PLUG-IN TYPEALARM DETECTORSE A SERIESINSTRUCTION MANUAL

Strany 2

- 10 -(2) Confirm that the Lock Release is lowered.(Fig. 3.2-2)(3) Insert the SE A series into the socket.(Fig. 3.2-3)When inserting, be carefulabout

Strany 3

- 11 -(4) Fix the SE A series and the socket by pushing the Lock Release up.(Fig. 3.2-4)3.3. Removal from a DIN Rail(1) Turn the power supply to the u

Strany 4 - Model Explanation

- 12 -(3) Separate the SE A series from the socket.(Fig. 3.3-2)(4) Remove the socket from the DIN rail by pulling the Socket Lock Release (at thebotto

Strany 5 - CONTENTS

- 13 -4. WiringWarningTurn the power supply to the instrument off before wiring.Working on or touching the terminal with the power switched on may res

Strany 6 - 1. Model

- 14 -1234-+5678-+CH1CPU13149101112-+-+-+CH2inputcircuitCH1inputcircuitInsulationcircuitInsulationcircuitInsulationcircuitInsulationcircuitDisplay/Set

Strany 7

- 15 -1234+-5678+-CPU13149101112-+-+-+Power supplyCH1A2outputCH2A2outputCH1A3outputCH2A3outputCH2outputcircuitPowercircuitDisplay/Settingkey circuitIn

Strany 8

- 16 -1234-+5678CH1CPU13149101112-+-+-+A1 outputA2 outputA3outputA4outputA5outputA6outputInputcircuitPowercircuitOutputcircuitOutputcircuitInsulationc

Strany 9 - 3. Mounting

- 17 -1234+-5678CPU13149101112-+-+-+A1 outputA2 outputCH1A3outputA4outputA5outputA6outputInputcircuitPowercircuitOutputcircuitOutputcircuitInsulationc

Strany 10

- 18 -910ACLoadInductive load (coil)Varistor, CR circuit, etc.910DCLoadDiode, varistor,CR circuit, etc.Inductive load (coil)4.3 Wiring of TerminalsWar

Strany 11

- 19 -Output specifications are shown below.Open collector Control capacity: 0.1 A 24 V DCAlarm output wiring example(Fig. 4.3.2-3)4.3.3 Input WiringC

Strany 12

- 2 -PrefaceThank you for purchasing the SE A series Alarm Detector. This manual containsinstructions for the mounting, functions, operations and note

Strany 13 - 4. Wiring

- 20 -5. Key Operation FlowchartSE2 APOWER ONRUN ModeCH1 CH2 CH1Alarm Setting GroupAlarm Setting GroupFunction GroupA1 value A1 value Input rangeScali

Strany 14

- 21 -CH2 Special FunctionFunction Group GroupA1 Energized/De-energized Setting items: Same as Set value lock: Energized CH1 function group. : Unlock:

Strany 15 - V( 1V) DC

- 22 -SE1 APOWER ONRUN ModeAlarm setting Function GroupgroupA1 value A4 value Input rangeScaling low limit to Scaling low limit to See (Table 5-3).Sca

Strany 16 - (Fig. 4.2-6)

- 23 -Special FunctionGroupA6 type A5 HOLD function Set value lockSee (Table 5-4). : OFF : Unlock: ON : Lock 1A1 Energized/De-energized : Lock 2: Ener

Strany 17

- 24 -6. SetupSetup should occur before using this unit, to set (or select) an Input range, Scaling low limitvalue, Scaling high limit value, Alarm ty

Strany 18

- 25 -(Table 6-2) SE1 ASetting Item Factory Default ValueK -200 to 1370 (SE1EA)Pt100 -200 to 850 (SE1RA)4 to 20 mA DC -1999 to 9999 (SE1AA)Input range

Strany 19

- 26 -Setting Item Factory Default ValueA1 delay timeA2 delay timeA3 delay timeA4 delay timeA5 delay timeA6 delay time0 secSpecial function group (Com

Strany 20 - 5. Key Operation Flowchart

- 27 -6.1 Indication after Power-onAfter power-on, the unit moves to warm-up status for approx. 3 seconds as shown belowin (Fig. 6.1-1) and (Fig. 6.1-

Strany 21 - A2 Energized/De-energized

- 28 -After that, the unit switches to RUN mode as shown below in (Fig. 6.1-3), (Fig. 6.1-4).SE2 A(Fig. 6.1-3)SE1 A(Fig. 6.1-4)6.2 Basic Operation of

Strany 22

- 29 -SetvalueInputvalue(1) RUN Mode(Fig. 6.2-1)(2) CH1 Function Group(Fig. 6.2-2)(3) Input Range Selection(Fig. 6.2-3)To set (or select)each item, us

Strany 23 - Special Function

- 3 -11..IInnssttaallllaattiioonnPPrreeccaauuttiioonnssCautionThis instrument is intended to be used under the following environmental conditions(IEC6

Strany 24 - 6. Setup

- 30 -6.3 Setup6.3.1 Function GroupFor the SE2 A, this is the function group for CH1.To enter the function group, follow the procedures below.(1) Pres

Strany 25

- 31 -Display Name, Function, Setting Range Factory Default ValueInput range (SE2RA, SE1RA) Pt100 -200 to 850• For the SE2RA and SE1RA, selects a RTD

Strany 26

- 32 -Display Name, Function, Setting Range Factory Default ValueScaling high limit 1370 (SE2EA, SE1EA)850 (SE2RA, SE1RA)9999 (SE2AA, SE2VA, SE1AA, SE

Strany 27

- 33 -Display Name, Function, Setting Range Factory Default ValueA1 type No alarm actionINOUT• Selects an A1 type.Note: If an A1 type is changed, the

Strany 28

- 34 -Display Name, Function, Setting Range Factory Default ValueA2 type No alarm actionINOUT• Selects an A2 type.Available for 6 points alarm output

Strany 29

- 35 -Display Name, Function, Setting Range Factory Default ValueA5 type No alarm actionINOUT• Selects an A5 type.Available for 6 points alarm output

Strany 30

- 36 -Display Name, Function, Setting Range Factory Default ValueA4 Energized/De-energized EnergizedINOUT• Selects A4 action Energized or De-energized

Strany 31

- 37 -Display Name, Function, Setting Range Factory Default ValueA4 HOLD function OFFINOUT• Selects OFF or ON for A4 HOLD function.If alarm HOLD is se

Strany 32

- 38 -Display Name, Function, Setting Range Factory Default ValueA3 hysteresis 1.0 (SE2EA, SE2RA, SE1EA, SE1RA)1.0% (SE2AA, SE2VA, SE1AA, SE1VA)INOUT•

Strany 33

- 39 -Display Name, Function, Setting Range Factory Default ValueA2 delay time 0 secINOUT• Sets A2 action delay time.A2 output does not turn ON until

Strany 34

- 4 -Model ExplanationModel names included in this manual are indicated below.Name ModelSE2 A SE2EA, SE2RA, SE2AA, SE2VASE A seriesSE1 A SE1EA, SE1RA,

Strany 35

- 40 -6.3.2 CH2 Function GroupAvailable only for the SE2 A.To enter the CH2 Function Group, follow the procedures below.(1) In the RUN mode, press the

Strany 36

- 41 -Display Name, Function, Setting Range Factory Default ValueDisplay selection CH1 input value/A1 value (SE2 A)Input value /A1 value (SE1 A)INOUT•

Strany 37

- 42 -SetvalueInputvalue7. Alarm Settings7.1 Basic Operation of Alarm SettingsAlarm settings are conducted in the Alarm setting groups.For the SE2□A,

Strany 38

- 43 -(2) Alarm Setting Group(Fig. 7.1-2)(3) A1 Value(Fig. 7.1-3)Press the key while theAlarm setting group charactersare being indicated.Please useth

Strany 39

- 44 -7.2 Alarm Settings7.2.1 Alarm Setting GroupFor the SE2 A, this is the alarm setting group for CH1.To enter the Alarm setting group, follow the p

Strany 40

- 45 -7.2.2 CH2 Alarm Setting GroupAvailable only for the SE2 A.To enter the CH2 alarm setting group, follow the procedures below.(1) In the RUN mode,

Strany 41

- 46 -8. Operation8.1 Indication after Power-onAfter power-on, the unit moves to warm-up status for 3 seconds as shown belowin (Fig. 8.1-1) and (Fig.

Strany 42 - 7. Alarm Settings

- 47 -(Table 8.1-1)Input DisplayInputKKJRSBETNPL-W5Re/W26ReW3Re/W25Re: -200 to 1370: 0 to 400: -200 to 1000: -50 to 1760: -50 to 1760: 0 to 1820: -200

Strany 43

- 48 -SetvalueInputvalueSetvalueInputvalue8.2 Unit OperationThe unit enters the RUN mode after 3-second warm-up indication as shown in(Fig. 8.2-1) and

Strany 44

- 49 -• Indication when Alarm Output is ONSE2 A:When alarm output is ON, the relevant channel indicator with current alarm outputON will flash, and th

Strany 45

- 5 ---- CONTENTS ---1. Model Page1.1 Model ---------------------------------------------------------------------------- 61.2 How to Read the Model La

Strany 46 - 8. Operation

- 50 -• Indication when input value is -200.0 (-2000) or lessWhen the range has a decimal point: For the indication of -200.0 or less, the input value

Strany 47

- 51 -9. SpecificationsInput SpecificationsSE2EA, SE1EA Input resistance: 1 M or moreExternal resistance: 100 or less, However, B: 40 or lessBurnout:

Strany 48

- 52 -Output SpecificationsSE2 A: Up to 3 points alarm output for each channel can beselected.SE1 A: Up to 6 points alarm output can be selected.For e

Strany 49

- 53 -PerformanceReference inputaccuracy (at 23 )SE2EA and SE1EA:Within 0.1% of each input spanR, S inputs -50 to 200 (-58 to 392 ): Within 6 (12 )B i

Strany 50

- 54 -10. Troubleshooting10.1 IndicationProblem Presumed Cause and SolutionThe Input display isflashing " " or" ".The input value

Strany 51 - 9. Specifications

- 55 -11. Character TableAlarm Setting GroupSE2 A: CH1 and CH2 have respective setting items.Display Setting Item Factory Default Value DataA1 valueA2

Strany 52

Display Setting Item Factory Default Value DataA5 HOLD functionA6 HOLD functionOFFA1 hysteresisA2 hysteresisA3 hysteresis1.0 (SE2EA, SE2RA, SE1EA, SE1

Strany 53 - Ambient temperature -5 to 55

- 6 -1. Model1.1 ModelSE A SeriesS E A- -2 E 2ch alarm detector (thermocouple)2 R 2ch alarm detector (RTD)2 A 2ch alarm detector (direct current) (*)2

Strany 54 - 10. Troubleshooting

- 7 -1.2 How to Read the Model LabelThe model label is attached to the left side of the case.SE2 AModel (E.g. SE2EA-1-0-0)CH1 input (Enter a range sel

Strany 55 - 11. Character Table

- 8 -2. Name and Functions of SectionsSE2 ASE1 A(Fig. 2-2)NoticeWhen setting the specifications and functions of this instrument, connect terminals 13

Strany 56 - SHINKO TECHNOS CO., LTD

- 9 -3. Mounting3.1 External Dimensions (Scale: mm)(Fig. 3.1-1)3.2 Mounting to a DIN Rail(1) Hook the upper part of the socket on the DIN rail, and mo