- 52 -
Output Specifications
SE2 A: Up to 3 points alarm output for each channel can be
selected.
SE1 A: Up to 6 points alarm output can be selected.
For each alarm output, one alarm type can be selected in [Alarm
type] from the following.
High limit alarm Low limit alarm
High limit alarm
with standby
Low limit alarm
with standby
Standby functions. Standby functions.
Alarm action
ON/OFF action
Alarm hysteresis SE2EA, SE2RA, SE1EA & SE1RA:
0.1 to 100.0 ( )
SE2AA, SE2VA, SE1AA & SE1VA:
0.1 to 100.0% of input span
Alarm delay time 0 to 9999 sec
Alarm
Energized/De-energized
Energized/De-energized, Selectable
Alarm HOLD function OFF/ON, Selectable
A1 output (SE2 A),
A1, A2 outputs
(SE1 A)
Relay contact, 1a
Control capacity 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos
=0.4)
Electrical life 100,000 cycles
A2, A3 outputs
(SE2 A),
A3 to A6 outputs
(SE1 A)
Open collector
Control capacity 0.1 A 24 V DC
ON
O
FF
A1 hysteresis
A1
value
ON
O
FF
A1 hysteresis
A1
value
ON
O
F
F
A1 hysteresis
A1
value
ON
O
FF
A1 hysteresis
A1 value